![]()
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
|
Common Questions
How Do I Size Batteries for a UPS application? Back To Top UPS batteries are sized to provide emergency back-up power to the UPS in the event of a total AC blackout. While it is often a matter of convenience or personal preference, the length of back-up time required is primarily a function of the process being protected. It is also governed by the cost of the battery.Since a UPS is utilized
to provide continuous power to a process of one kind or another, the batteries
should be sized to carry the load for as long as it takes to either complete
the process, perform an orderly shut-down of the process, or bring a generator
on-line to power the load. A UPS inverter converts DC power to AC power.
The battery must be sized large enough to provide the DC input power (in
kilowatts) for a fully loaded inverter for the specified length of time.
The DC input power is determined by applying the load power factor, and
inverter conversion efficiency to the inverter's AC power rating.
Using discharge tables
supplied by the battery manufacturer(s), select the type of battery that
meets the above requirements of 0.307 kilowatts per cell. What Are The Advantages/Disadvantages of Different Battery Technologies? Back To Top There are several
different types of batteries available for UPS applications. However,
they basically breakdown into two technologies: Lead Acid and Nickel Cadmium.
Lead acid batteries are further divided into two types: Lead Calcium and
Lead Antimony. Lead Calcium batteries can be broken down into two categories:
traditional wet cell (or flooded) and valve regulated lead acid, (or VRLA-sometimes
mistakenly referred to as maintenance free). The proper battery for a
given application is dependent upon a number of factors. (Refer to Table
1 below for a quick comparison between battery technologies.)
FOR MORE INFORMATION, GO TO SELECTION AND SIZING OF BATTERIES FOR UPS BACKUP FOUND IN THE TECHNICAL PAPERS SECTION OF THIS SITE. Why Fuses Instead of Breakers For UPS Distribution Panels? Back To Top The goal of any well
designed UPS system is to maintain power to the load at all times. However,
since the output of the UPS is generally fed through a distribution panelboard
to the load, there may be times when an overload or fault occurs on one
or more branch circuits that has the potential for dropping the load(s)
on that branch. This condition needs to be limited to only that branch,
and not affect any other loads, or upstream electrical equipment! Therefore,
it is imperative that the fault condition be cleared as quickly as possible.
Most molded case breakers, used as branch breakers in panelboards, take
2-3 cycles (50 milliseconds) before they will open under short circuit
or fault conditions. Fast-acting fuses, such as the Gould Shawmut A25X,
however, have much faster clearing characteristics, typically 1/4 cycle
(4 milliseconds). FOR MORE INFORMATION,
GO TO UPS
PLANNING AND INSTALLATION GUIDE FOUND IN THE TECHNICAL
PAPERS SECTION OF THIS SITE. What Is Ferroresonant? Back To Top A ferroresonant transformer
is a non-linear transformer that is designed to provide passive
voltage regulation, using magnetics only; that is, without any complex
feedback circuits to monitor and adjust the output voltage level. It is
designed to operate within a preset regulation band; typically set anywhere
from 1%-4%. A non-linear transformer differs from a linear transformer
in that the output voltage will not deviate outside of this regulation
band, regardless of what happens on the input. The output of a linear
transformer, on the other hand, is as the term implies, directly proportional
to the input. That is, whatever happens on the input will directly affect
the output. FOR MORE INFORMATION,
GO TO TECHNICAL
PAPERS SECTION OF THIS SITE. What Is Pulse-Width-Modulation (PWM)? Back To Top A PWM inverter, unlike
the ferroresonant type, employs high speed switching power devices to
generate a series of "pulses" in the inverter bridge to "simulate"
a sine wave. This signal is then filtered and fed to the load through
a linear transformer. Because the PWM employs a non-regulating linear
transformer (rather than a non-linear regulator such as the ferroresonant
type), a fairly complex network of feedback circuits is required to maintain
the output voltage and current at the correct levels for the load. FOR MORE INFORMATION, GO TO THE TECHNICAL PAPERS SECTION OF THIS SITE.
What Is A UPS? Back To Top A UPS is an electrical
device that provides continuous, conditioned, uninterrupted power to a
critical AC load. It also provides isolation between the input and the
output. It consists of a Rectifier/Battery Charger, Battery System, and
Inverter. The Battery Charger converts incoming commercial/utility AC
power to DC power. This power is then supplied both to a Battery system
and an Inverter. The Inverter then converts this DC power back into AC
power which is fed to the critical load(s). The Battery is an emergency
DC supply that is connected in parallel with the output of the Battery
Charger, and supplies the DC power to the Inverter (without any switching)
in the event that the incoming commercial power is lost or outside of
specified tolerances. What Is The CBEMA Curve and What Does It Mean? Back To Top CBEMA stands for Computer Business Equipment Manufacturer's Association. The CBEMA curve defines the voltage tolerance levels and duration that computers and other electrical control devices, such as Programmable Logic Controllers (PLCs) can safely operate within without corruption of data. The curve shows that voltage transients of certain magnitudes, say 250%, are acceptable for short periods of time-100 microseconds. That same transient with a duration of say 1/2 cycle (8.33 milliseconds) would cause disruption of data. The curve also shows that voltage levels below nominal are also acceptable, provided they do not exceed the magnitude and duration defined by the curve. For example, a voltage deviation of up to -30% held for that same 1/2 cycle, would not cause a disruption of data. Indeed, the curve shows that voltage levels of even zero can be tolerated for a very brief period of time - say 4 milliseconds (1/4 cycle). By the way, that same zero voltage level sustained for longer than 1/4 cycle could wreak havoc on data. Losing voltage for only a little more than 1/4 cycle (8.33 milliseconds) seems insignificant, but for a computer, or other extremely sensitive equipment, it can be a lifetime. The significance of
the CBEMA curve in UPS applications is important when considering a UPS
(or inverter) with an electronic (static) transfer switch. This switch
is very critical to the overall reliability and up time of the UPS (and
its load) because it is able to transfer the load off the Inverter to
an alternate AC power source to clear downstream faults when necessary,
or in the event of an Inverter failure. The ability to do this quickly
and seamlessly is vital to the load. This seamless transfer must take
place in both directions. Most static switches are designed to retransfer
the load back onto the Inverter after the fault or overload has been cleared.
This retransfer should also cause no disruption of power. But, inevitably,
there is a voltage deviation of some magnitude and duration when making
this transfer. Therefore, it is extremely important to understand the
implications of these voltage deviations. As has been pointed out, a voltage
deviation of up to 30%, for example, can be tolerated for up to 1/2 cycle
or more. Much has been made in the past of Inverters that display a "lower"
voltage deviation (commonly referred to as transient response) than some
other types of Inverters. However, the CBEMA curve shows that electronic
devices don't care whether the level is higher or lower, just as long
as it is within acceptable limits. How Do I Size My UPS? Back To Top Obviously, a UPS is designed and sized to provide continuous power to an AC load. The word continuous is a key word because many AC loads, such as motors, require a great deal more power (current) during start-up, than the actual "running" current. A typical rule of thumb is that start-up current for a motor, commonly referred to as "locked rotor current" is 8-12 times the actual running or steady-state current; otherwise you could end up with a UPS that is 8-12 times larger than what your load actually requires. It will be shown below how to avoid this problem when sizing your UPS. The current measurement
used to determine the load is the RMS value, rather than
the peak value. (Note: If only the peak value is known,
the RMS value can be determined by multiplying the peak value times 0.707).
Once the load current is determined, the capacity of the UPS can be determined
simply by multiplying the RMS current times the RMS voltage. This result
is the Volt Ampere (VA) capacity required of the UPS. On 3-phase systems,
multiply the result by A phenomenon associated with today's electronic loads, such as computer, and control devices, is the introduction of switch-mode power supplies. These power supplies are non-linear in nature, and exhibit what is known as a crest factor. The crest factor is the ratio of the peak value of current to its corresponding RMS value. These crest factors can be anywhere from 1.414 (the ratio of peak to RMS current for a perfect sine wave), to 3 or 4, depending on the non-linearity of the load. However, for all practical situations, the crest factor is typically seen as 2-2.5. Most UPS systems utilize a static (or electronic) transfer switch to transfer the load to an alternate AC source in the event that of a fault or overload occurs that is beyond the overload rating of the Inverter (typically 120%). In addition, most of these static switches have designed-in crest factor logic that differentiates between a true overload and a crest factor that results from a switching power supply. This prevents the static switch from making "nuisance" transfers back and forth from the inverter to the alternate source. Therefore, although some manufacturers of DCS and other controls systems recommend that the UPS be sized to accommodate the crest factor, it is not necessary to do so. As stated previously, the UPS need only be sized for the RMS current. Likewise when looking
at motor applications, or other loads, that require a large amount of
inrush current, the static switch allows the load to be started on the
alternate source rather than the inverter. Once the load is stabilized,
the static switch can then transfer the load onto the UPS inverter. That
way, you can avoid the need for oversizing the UPS, and incurring unnecessary
costs. Why Single Phase Instead of Three Phase? Back To Top UPS systems are available in a variety of single phase, three phase, and so-called split phase voltage configurations. However, many loads in the Industrial market are single phase only - particularly DCS and PLC applications. In years past, the EDP market - especially large main frame computer applications gave rise to a need for three phase UPS systems. There are, obviously, some three phase industrial loads, notably large motors, but by and large most industrial situations require single phase. This is actually good news, because a single phase UPS offers some advantages over three phase systems. First, the fault clearing capability of a single phase inverter is approximately three times greater than a three phase unit. This is especially true with ferroresonant inverters which have nearly four times the fault clearing capability of other types of inverters. Downstream fault protection coordination is also easier to accomplish with single phase. Second, there are no loads to balance. When using a three phase inverter to drive single phase loads, care must be taken that loads are balanced within a few percent of each other, particularly with non-ferroresonant inverters. Load imbalance can lead to voltage regulation that is out of spec, as well as increased harmonics, which can lead to distortion in the output waveform and/or overheating. Single phase distribution panelboards and switchboards are less expensive, smaller, and easier to work with than three phase units. Again, since industrial controls systems for the most part consist of single phase loads it probably doesn't make a lot of sense to install three phase panels and inverters in the distribution system. This is likewise true for so-called split phase distribution systems. Many panelboards are rated for 120/240 volt operation. Therefore, many electricians think that they need to provide an inverter (UPS system) with a 120/240 volt output, rather than a straight 120 volt output, even though the actual loads are only 120 volts. In reality, a 120 volt unit is what they need - all they need to do is split the loads at the panel board. Many panelboard manufacturers will make a straight 120 volt panel if requested to so, usually at no extra cost. Although it may be a trade-off at higher power levels, it can be easier and less expensive to run cables for a single phase system. The trade-off comes when taking into consideration the breakers and cable sizes. In general, unless you truly have some three phase loads, then, it is usually a better bet to use a single phase UPS, rather than three phase. Check with your UPS supplier to make sure that they can provide a single phase system, even at higher power levels - say 75 or 100 kVA. Even at those ratings, the advantages of single phase may outweigh the perceived installation cost savings of three phase. |
|||||||||||||||||||||||||||||||||||||||||||||||||||
The Columbus Ohio and Rosario, Argentina facilities are ISO 9001 Certified. Click on the ISO World sign to the left to view current certificate. |
||
![]() |
World Headquarters: 875 Dearborn Drive, Columbus, Ohio 43085 Phone: 1-614-846-7500 1-800-635-7300 Fax: 1-614-885-3990 |
Asian Pacific Headquarters: AMETEK Singapore Office Solidstate Controls 43 Changi South Ave 2 #04-01 Singapore 486164 Phone: 65-6484-2388 Fax: 65-6481-6588 |
| Latin American/ South American Headquarters: Olive 1954 2000 Rosario, Argentina Phone: +54-341-455-3332 Fax: +54-341-454-0142 |
Mexico Office: Avenida Ejercito Nacional Number 423 2o. piso Colonia Granada C.P. 11520 Deleg. Miguel Hidalgo, Mexico, D.F. Phone:+52 55 5250 1232 |
|
Visit our Websites: English: www.solidstatecontrolsinc.com Nuclear: www.nuclearups.com Spanish: www.solidstatecontrolsinc-esp.com Russian: www.solidstatecontrolsinc-ru.com Chinese: www.solidstatecontrolsinc-chn.com Brazilian Portugese: www.solidstatecontrolsinc-bz.com |
||